A.O. Smith AIN slave
Overiview
This driver supports the A.O. Smith Advanced Internal Network (AIN) slave protocol. Some notes of interest are:
-Supports both comercial and residential A.O. Smith gas and electric products.
-A range of master parameters in one block may be read or written by configuring a single service object.
– May be connected along with ohter modules on the network including local and remote displays and other interface devices.
Slave settings
Baud rate
Select the desired network and baud rate
Parity
Fixed at not parity (1stop Bit)
 
Node Settings
Address
Fixed at 16
Service Object Settings
The AIN slave driver uses service objects to define the parameter values to capture from the master (“reading”) and to modify (“writing”). Each device object can access a renge of parameters located in one block on the master device. When reading is enabled, the driver will compare values into the database. When writing is enabled, the driver will generate a write command to the master when data values changes occur in database locations encompassed by a service object.
Description
This 32-character (max) field is strictly for user reference: it is not used at any time by the driver
 
Block Number
Indicates the nlock number (0…29) in wich the desired parameters are located.
 
Start Parameter
Defines the starting parameter number (0…255) for a range of parameters associated with this service object.
Number of Parameters
Defines the number of parameters (1…255) associated with this service object.
Database Address
Defines the database address where the first parameter of this device object will be mapped. The configuration studio will not allow entry of starting address that will cause, the service object to run past the end of the database. The highest calid database address, therefore, depends on the numer of parameters to be accessed.
 
Data Type
Fixed at 16-Bit Unsigned
Multiplier
The amount that associated network values are scaled by prior being stored into the databaseor after being retrieved from the database. Upon retrieval from the database, raw data is multiplied by the multiplier to produce a network (to be sent on this device). Similarly, network values (read from the device) are devided by the multiplier before being stored into the database.
Read Parameter
Check to enable reading (capturing the values of parameters from a broadcast). All read-enabled service objects are used to compare block and parameter number for each master broadcast.
Write Parameter
Check to enable writing: when values encompasses by this service object change in the internal database these changes will be written to the master on the next poll request.
ANC Gateway Converter Series interfaces A.O Smith to various Industrial Protocols including Profibus which is available in the ANC-500, Serial to Profibus Converter. ANC Gateway Converters interface to the following protocols:

RS485 Serial Protocols: The ANC-300e Gateway has the flexibility to choose Modbus Master/Slave as well as other RS485 serial protocols which include: Modbus Sniffer, A.O. Smith AIN, A.O. Smith PDNP, BACnet MS/TP Client, BACnet MS/TP Server, TCS Basys Master, MSA Chillgard Monitor, DMX 512-Master, DMX-512 Slave, M-Bus Master, Metasys N2 Master, Metasys N2 Slave, Siemens FLN Master, Siemens FLN Slave, Sullair Master, Toshiba ASD Master, Toshiba PLC Master.

Ethernet Protocols: The ANC-300e Gateway can communicate with the above RS485 protocols to Ethernet; and Ethernet to Ethernet protocols including Ethernet/IP Client/Server, AB CSP Ethernet Client/Server, Modbus TCP/IP, Profinet IO, BACnet/IP BBMD, BACnet/IP Client, BACnet/IP Server, Baumer VeriSens Client, CC-Link IE SLMP Client, MELSEC Client/Server, Generic Socket Client/Server & GreenFumeHood Client.

ANC-500 PROFIBUS TO MODBUS RTU / MULTIPLE SERIAL PROTOCOL GATEWAY CONVERTER

The Automation Networks ANC-500 PROFIBUS DP-V1 Gateway allows information to be transferred seamlessly between PROFIBUS and RS-485 networks with minimal configuration requirements. The ANC-550 provides a PROFIBUS port (DB-9 female connector) and an RS-485 port (4-wire terminal block style). The RS-485 port supports multiple protocols. PLC-style logical, arithmetic and filtering database manipulation operations allow the construction of complex autonomous data conditioning functions.

The ANC-550 is a part of the ANC Gateway Series product family. The ANC platform is designed to provide a uniform interface, configuration and application experience. This commonality reduces the user’s learning curve, reducing commissioning time while simplifying support.

The ANC-550 is a user-configurable multiprotocol Profibus DPV1 / RS-485 communications gateway, which allows seamless bridging between Profibus networks and various popular RS-485 based industrial and commercial communication networks.

ANC-500 Highlights using the Microsoft Windows®-based ICC Configuration Studio include:

 

  • Configure protocols, network characteristics, and client/server object definitions
  • Graphically interact with the internal database in real-time
  • Automatically update device firmware
  • Define autonomous internal elements such as database logic and object failsafe values
  • Capture, display and save serial network traffic with microsecond-precision timestamps The ANC-500 incorporates a variety of leading-edge automation technology elements, such as:
  • Power can be supplied via the USB cable (for configuration at a workstation) or as a 7-24VDC input on the main terminal block
  • Profibus DP-V1 support for both cyclic and acyclic (class 1 and class 2) communications
  • Acyclic access to entire internal database as 8-bit, 16-bit or 32-bit data types
  • Controlled by a powerful 32-bit processor · User-configurable network timeout behaviors
  • USB connectivity with virtual COM port support
  • 2-wire / 4-wire RS-485 network supports baud rates up to 115.2kbaud
  • Desktop, panel/wall and DIN-rail mountable (all hardware included)
  • Supports all Profibus baud rates
  • Supports up to 368 bytes of combined Profibus input and output cyclic data Flexible, Powerful and Easy-to-Use Profibus DP-V1 Gateway

 

For more product details contact Automation Networks at
www.automation-networks.es
info@automation-networks.es
(Tel) 281 771-0019