ANC-100e Wonderware ABCIP DAServer, Ethernet/IP to Data Highway Plus Application Note

This document provides information on how to setup the Automation Networks ANC-100e with a PC running Wonderware ABCIP DAServer on Ethernet/IP for communications to a PLC-5 on AB’s DH+. 

The ANC-100e will communicate with many devices that are DH+ nodes which include AB Panelviews, SLC 5/04s, and PLC-5s etc.

          • Note: Before proceeding, make sure
                    • Network adapter is correctly configured to access ANC-100e
                    • ANC-100e is connected to the PC or Ethernet network and DH+ network.

 

 

        1. Open System Management Console
        2. Select DASABCIP
        3. Right click the “Configuration” and select “add PORT_CIP Object”

wonderware1

4. Right click the “New_PORT_CIP_000” and select “add ENB_CLX Object”

wonderware2

        1. Entry the ANC 100e IP address in the Host Name Box. Default IP address is 192.16.0.230
        2. Right click the “New_ENB_CLX_Object” and select “Add BACKPLANE_CLX Object”

wonderware3

        1. Right click the “New_BACKPLANE_CLX Object” and select “Add DHRIO_CLX Object”

wonderware4

        1. The Slot Number can be found in RSLINX
        2. Right click the “New_ DHRIO_CLX Object” and select “Add PORT_DHP Object”

wonderware5

        1. The Channel Number, DH Plus Node Address and Link ID can be found in RSLINX
        2. Right click the “New_ DHRIO_CLX Object” and select “Add SLC500_DHP Object” or “Add PLC5_DHP Object”

wonderware6

        1. Entry the DH+ node address of the PLC5 or SLC500

wonderware7

        1. Create one Device Group
        2. Right click the “Archestra.DASABCIP.4” and select “Activate Server”

wonderware8